DUNGS Valve Proving System VPS 504 Series
01 May 2023
![DUNGS Valve Proving System VPS 504 Series](https://cdn1.npcdn.net/image/1682946199376dbcbf75c44b8c7366b6a438bd0a6d.jpg?md5id=d61a328561119583444e250036006e81&new_width=1190&new_height=1000&w=1518579331)
![DUNGS Valve Proving System VPS 504 Series](https://cdn1.npcdn.net/image/1682946199376dbcbf75c44b8c7366b6a438bd0a6d.jpg?md5id=d61a328561119583444e250036006e81&new_width=1190&new_height=1000&w=1518579331)
View Full Size
Valve testing system VPS 504 for multiple actuators
Valve proving system for automatic shutoff valves as per EN 161, Class A and Class B
Valve proving system for automatic shutoff valves as per EN 161, Class A and Class B
The VPS 504 may be used with any other valve whose tightness in counter-flow direction excludes by construction a leakage in flow direction.
The VPS 504 is suitable for all DUNGS valves according to EN 161 Classes A and B.
The VPS 504 is the valve proving system for DUNGS multiple actuators. The valve proving system complies with EN 1643:
- Equipment operates independent of residual pressure in the range of the permissible operating range.
- Test volume ≤ 4 l
- Setting work not necessary on site
- Short test period: ≈ 10 s, max. 36 s
- Tightness or leaks are displayed by an LED
- External fault display possible for series 02, series 04 and S05
- Group fault alarm optional for S01 (SSM)
- Suitable for TRD systems
- Electrical connection possible by plug connection S01, 02, 03. No rewiring is required for contact allocation as per DIN 4791.
- S04 and S05: electrical connection at screw terminals via PG 13.5 cable entry